Atmosphere® Duct Liner

Excellent sound absorption, temperature control and energy conservation in sheet metal ducts — this liner does it all. It’s faced with a tightly bonded mat to give the airstream a smooth surface, resisting damage during installation and operation.

Applications

Certifications
Product Features
Proven Performance
Delivering proven strength against air erosion testing at over 170 miles/hour — 15,000 ft./min. — for trusted temperature and sound control in metal ducts.
Quality Design
Built with a tough, tightly bonded mat facing, this liner is fire-resistant, non-corrosive, durable and resilient. Designed to withstand damage from normal handling and shop abuse.
ECOSE® Technology
Our patented, bio-based binder is a smarter alternative to using phenol formaldehyde. It’s been foundational in our commitment to sustainability.
Product Details
Technical Data
Technical Data
Property (Unit) Test Performance
Corrosiveness ASTM C665 Does not accelerate corrosion of steel 
Corrosion ASTM C1617 Pass 
Maximum Service Temperature ASTM C411 250° F (121° C) 
Air Velocity ASTM C1071 Max. 6,000 ft./min. (30.5 m/sec.)
Tested to 15,000 ft./min. (76.2 m/sec.)
Water Vapor Sorption (by weight) ASTM C1104 Less than 3%
Mold Growth ASTM C1338, UL 2824, ASTM G21, ASTM G22 Pass
Surface Burning Characteristics (flame spread/smoke developed) ASTM E84, UL 723, CAN/ULC S102 FHC 25/50; UL Classified
Forms Available, Thermal Conductance “C”*, and Resistance “R”†
Forms Available
Density Thickness** Width  Length
1.5 PCF
(24 kg/m³)
1" (25 mm) 34"–36"* (864 mm–915 mm)
46"–48" (1168 mm–1219 mm)
56"–72" (1422 mm–1829 mm)
50' (15.24 m)
100' (30.48 m)
140' (42.67 m)
200' (60.96 m)
2.0 PCF (32 kg/m³) 1.5" (38 mm) 50' (15.24 m)
90' (27.43 m)
2" (51 mm) 50' (15.24 m)
100' (30.48 m)
0.5" (13 mm) 100' (30.48 m)
1" (25 mm) 50' (15.24 m)
100' (30.48 m)

*Widths of 34"–36" not available with edge coating.
**Non-standard widths for all 0.5", 1", 1.5", and 2" products from 34"–36", 46"–48" and 56"–72" are available in 25" (6.35 mm) increments of minimum order quantity.
Thermal Conductance “C”* and Resistance “R” (ASTM C177)
Mean Temperature 75° F (24° C)
Product Conductance "C" Resistance "R"
1.5 PCF
(24 kg/m³)
1" (25 mm) 0.24 (1.42) R-4.2 (0.74)
1.5" (38 mm) 0.17 (0.97) R-6.0 (1.06)
2" (51 mm) 0.13 (0.74) R-8.0 (1.41)
2.0 PCF
(32 kg/m³)
0.5" (13 mm) 0.48 (2.73) R-2.1 (0.37)
1" (25 mm) 0.24 (1.36) R-4.2 (0.74)
1.5" (38 mm) 0.16 (0.91) R-6.3 (1.11)
“C Units” BTU ft2 ∙  hr  ∙ ˚F (W m2 ∙ ˚C) “R Units” ft2 ∙  hr  ∙ ˚F BTU( m2 ∙ ˚C W)

*The lower the value, the better the performance. The higher the value, the better the performance.
 
Sound Absorption Coefficients
 
Sound Absorption Coefficients | ASTM C423, Type A Mounting
Type Octave Band Center Frequency (cycles/sec.)
125 250 500 1000 2000 4000 NRC
1.5 PCF)
(24 kg/m)
1" (25 mm) 0.18 0.28 0.73 0.85 0.91 0.90 0.70
1.5" (38 mm) 0.23 0.50 0.87 0.92 0.93 0.93 0.80
2" (51 mm) 0.37 0.76 1.02 1.00 0.98 0.92 0.95
2.0 PCF
(32 kg/m3)
0.5" (13 mm) 0.10 0.17 0.43 0.59 0.73 0.75 0.50
1" (25 mm) 0.25 0.35 0.69 0.89 0.96 1.01 0.70
1.5" (38 mm) 0.27 0.55 0.87 0.99 1.00 0.98 0.85

Coefficients determined per ASTM E795 Type A Mounting.
NOTE: ASHRAE Handbook for HVAC Applications – Sound and Vibration Control contains insertion loss values for lined sheet metal ducts.
Friction Loss
 
Friction Loss  |  Inches of Water Per 100'
Ft./min. Hydraulic Diameter
Velocity 10" 16" 24" 32" 40" 72" 100"
500 0.054 0.030 0.018 0.012 0.009 0.005 0.003
600 0.077 0.042 0.025 0.018 0.013 0.007 0.004
700 0.104 0.057 0.034 0.024 0.018 0.009 0.006
800 0.134 0.074 0.044 0.031 0.023 0.011 0.008
900 0.169 0.093 0.056 0.039 0.029 0.014 0.010
1000 0.207 0.114 0.068 0.048 0.036 0.018 0.012
2000 0.806 0.443 0.266 0.186 0.141 0.069 0.046
3000 1.797 0.988 0.594 0.415 0.315 0.153 0.103
4000 3.179 1.748 1.050 0.734 0.557 0.271 0.181
5000 4.952 2.724 1.636 1.143 0.867 0.422 0.283
Mechanical Fastener Location and Liner Interior Width
Mechanical Fastener Location
Velocity per ft./min. (m/sec.) 0-2500
(0-12.7)
2501-5000
(12.7-25.4)
A. From corners of duct 4" (102 mm) 4" (102 mm)
B. From transverse end of duct liner 3" (76 mm) 3" (76 mm)
C. Across width of duct, on centers (min. 1/side) 12" (305 mm) 12" (305 mm)
D. Across length of duct, on centers (min. 1/side) 18" (457 mm) 18" (457 mm
 
Liner Interior Width
No. Pins inches (mm)
0 ≤ 8 ≤ 203
2 9-16 229-406
3 17-28 432-711
4 29-40 737-1016
5 41-52 1041-1321
6 53-64 1346-1626
7 65-76 1651-1930
8 77-88 1956-2235
9 89-100 2261-2540
Customer Reviews
Need More Product Support?
Reach out to our technical support team for product specs, installation guidance and more.
Contact Tech Support
Related Products
Atmosphere® Rigid Plenum Liner
Duct liner board delivers efficient sound absorption, low thermal conductivity and minimal air surface friction.
Applications
Thickness
1"; 1.5"; 2"
Length
48" - 120"
Width
24"; 48"
Atmosphere® Duct Wrap
Designed to wrap the duct, providing excellent thermal properties, energy conservation and condensation control.
Applications
Thickness
1.5" - 3"
Length
50' - 100'
Density
0.75 PCF - 1.5 PCF
Atmosphere® Air Duct Board
Validated formaldehyde-free board used to fabricate the complete air duct, providing excellent acoustic insulation.
Applications
Thickness
1"; 1.5"; 2"
R-Value
4.3; 6.5; 8.7
Stiffness
EI-475; EI-800
Here To Help
Always working to meet your needs. With answers to your product questions and more, we’ve got you covered.
Contact Us